WANGYUAN LV Fuse Cutout with Fuse Link are designed for overcurrent protection in low-voltage distribution networks. Made of durable engineering plastic housing with brass or copper alloy contacts and ceramic/glass fuse elements, the modular plug-in structure ensures reliable circuit interruption and safe field maintenance. Available in multiple current ratings from 32A to 400A, all products comply with relevant international standards, suitable for industrial, commercial and utility low-voltage applications.
Specification
Overhead LV fuse Cutout
Introduction
The cutout bases and fuse carriers shall have the following current ratings at 230/400V: Three phase and neutral for transformers up to 500kVA: 400A; and Three phase and neutral for transformers above 500kVA:630A.
Housing
The outer housing of the units shall be comprised of Grey insulating material of sufficient mechanical strength as to prevent it from becoming damaged. The material shall be resistant fo ultra violet degradation and have flame retardant properties. The Grey colour shall be RAL 7035 code system according to DNA (German Standards Board, Frankfurt, Germany).
Fuse Carrier
The fuse carrier shall be required to take J.? type cartridge fuse links with 82mm centers, conforming to BS 88. Tightening screws shall have insulated tops to enable the fuse carrier to be removed without safety devices (rubber gloves, etc.)

Wedge fuse link
WEDGE FUSE LINK J-TYPE

| Item |
JHU |
JPU |
JSU |
| Rated voltage |
415/500V AC |
415/500V AC |
415/500V AC |
| Rated breaking capacity |
50kV |
50kV |
50kV |
| Standard |
IEC 60269-2-1 BS 88-2 |
IEC 60269-2-1 BS 88-2 |
IEC 60269-2-1 BS 88-2 |
| Class |
Gg/Q1 |
Gg/Q1 |
Gg/Q1 |
| Rated current |
20A-800A |
20A-800A |
20A-800A |
HRC FUSE LINK with central tags

| Item |
TBC |
TM |
TT |
| Rated voltage |
5000V AC |
5000V AC |
5000V AC |
| Rated breaking capacity |
80kV |
80kV |
80kV |
| Standard |
BS 88-2, IEC 60269-2-1 |
BS 88-2, IEC 60269-2-1 |
BS 88-2, IEC 60269-2-1 |
| Class |
Gg/Q1 |
Gg/Q1 |
Gg/Q1 |
| Rated current |
2A-63A |
500A-630A |
500A-630A |
Low Voltage H.R.C fuse
Basic Data

| Model |
Domestic and oversea similar products |
Rated Voltage(V) |
Rated Current(A) |
Overall dimension(mm) |
| A |
B |
C |
D |
F |
G |
| 76JPU |
RG8M |
415/500 |
20-250 |
100 |
76 |
45 |
40 |
14 |
13 |
| 82JPU |
RG8M |
415/500 |
20-400 |
111 |
82 |
45 |
40 |
14 |
17 |
| 92JPU |
RG8M |
415/500 |
40-630 |
131 |
92 |
45 |
56 |
17 |
20 |

| Model |
Domestic and oversea similar products |
Rated Voltage(V) |
Rated Current(A) |
Overall dimension(mm) |
| A |
B |
C |
ΦD |
E |
F |
H |
2-Φd |
| RG11 |
RGS11 |
250/380 |
32 |
56 |
42 |
27.5 |
16.5 |
12.5 |
2 |
17.5 |
6.5×9 |
| RG4(Z) |
RGS4(Z) |
500/690 |
63 |
77 |
62 |
49.5 |
16.5 |
12.5 |
2 |
18 |
6.5×9 |
| RG44(Z) |
RGS44(Z) |
415/500 |
100 |
94 |
72 |
32.5 |
25 |
18 |
2 |
21.5 |
11×14 |
| RG7(Z) |
RGS7(Z) |
415/500 |
100 |
113 |
94 |
68 |
34 |
19 |
2 |
35 |
9×11.5 |
HIGH-VOLTAGE FUSE LINK SERIES

| Rated current(A) |
Dimension (mm) |
Quantity/carton |
| A |
B |
C |
D |
F |
| 1-25 |
12.5+0.2 |
19.0+0.2 |
Notel |
2 |
6.5 |
250 |
| 30-40 |
12.5+0.2 |
19.2+0.2 |
Notel |
3 |
8 |
250 |
| 50-100 |
19.0+0.3 |
Not applicable |
Notel |
5 |
9 |
250 |
| 140-200 |
19.0+0.3 |
Not applicable |
Notel |
7 |
13 |
150 |
Advantages
Electrical Protection
The ceramic/glass fuse link with precision-calibrated fuse element delivers stable overcurrent interruption. Silver-plated copper contacts ensure low contact resistance and consistent tripping performance across the rated range.
Mechanical Strength
The engineering plastic housing offers high impact resistance and dimensional stability under thermal cycling. Robust terminal connections and spring-loaded contacts maintain secure clamping under vibration and load fluctuations.
Corrosion Resistance
All metal contacts are silver or nickel plated with anti-oxidation treatment for long-term reliability. The sealed housing and insulated pull-rod sleeve protect internal components from moisture, UV and environmental contaminants.
Installation & Versatility
Modular plug-in design enables quick fuse link replacement without tools. The remote pull-rod mechanism allows safe operation from a distance, compatible with standard LV distribution panels and pole-mounted configurations.